R HOUSE--GENERAL PLAN OF COAL BUNKERS AND ECONOMIZERS.] [Illustration: 58TH ST. POWER HOUSE--GENERAL PLAN OF MAIN OPERATING FLOOR.] The six chimneys, spaced 108 feet apart, and occupying the space between the ends of the adjacent coal bunkers, are supported on plate-girder platforms in the fifth floor, leaving the space below clear for a symmetrical arrangement of the boilers and economizers from end to end of the building. The platforms are framed of single-web girders 8 feet deep, thoroughly braced and carrying on their top flanges a grillage of 20-inch I-beam. A system of bracing for both the chimney platforms and coal bunkers is carried down to the foundations in traverse planes about 30 feet apart. The sixth tier of beams constitute a flat roof over a portion of the building at the center and sides. In the engine room, at this level, which is 64 feet above the engine-room floor, are provided the two longitudinal lines of crane runway girders upon which are operated the engine-room cranes. Runways for 10-ton hand cranes are also provided for the full length of the boiler room, and for nearly the full length of the north panel in the engine room. Some of the loads carried by the steel structure are as follows: In the engine house, operating on the longitudinal runways as mentioned, are one 60-ton and one 25-ton electric traveling crane of 75 feet span. The imposed loads of the steam-pipe galleries on the south side and the switchboard galleries on the north side are somewhat irregularly distributed, but are equivalent to uniform loads of 250 to 400 pounds per square foot. In the boiler house the weight of coal carried is about 45 tons per longitudinal foot of the building; the weight of the brick chimneys is 1,200 tons each; economizers, with brick setting, about 4-1/2 tons per longitudinal foot; suspended weight of the boilers 96 tons each, and the weight of the boiler setting, carried on the first floor framing, 160 tons each. The weight of structural steel used in the completed building is about 11,000 tons. [Sidenote: _Power House Superstructure_] The design of the facework of the power house received the personal attention of the directors of the company, and its character and the class of materials to be employed were carefully considered. The influence of the design on the future value of the property and the condition of the environment in general were studied, together with the factors relati
PREV.   NEXT  
|<   48   49   50   51   52   53   54   55   56   57   58   59   60   61   62   63   64   65   66   67   68   69   70   71   72  
73   74   75   76   77   78   79   80   81   82   83   84   85   86   87   88   89   90   91   92   93   94   95   96   97   >>   >|  



Top keywords:
weight
 

engine

 
carried
 

longitudinal

 
building
 
platforms
 
boiler
 

boilers

 

design

 

provided


setting

 

girders

 

galleries

 

economizers

 

chimneys

 

length

 

GENERAL

 

bunkers

 

cranes

 

uniform


operating

 

mentioned

 

pounds

 

runways

 
irregularly
 
traveling
 

electric

 

imposed

 

distributed

 

switchboard


equivalent

 
structural
 
employed
 

carefully

 

considered

 

materials

 

directors

 

company

 

character

 
influence

future
 
studied
 

factors

 

relati

 
general
 

environment

 

property

 

condition

 

attention

 
personal